Monitoring parameter registers – GE Industrial Solutions AF-300 G11 User Manual

Page 138

Advertising
background image

12-3

Data subject to change without notice 7/07. © 2007 GE Drives

Monitoring parameter registers

Address Code

Description

Unit

Range

Min. unit

Read

Data

/ Write

Format

2049

M01

Frequency command (final
command)

-

- 20000–20000 (max. frequency
at ± 20000)

1

R

2

2053

M05

Frequency command (final
command)

Hz

0–400.00 0.01

R

5

2054

M06

Actual frequency

-

- 20000–20000

1

R

2

(max. frequency at ± 20000)

2055

M07

Actual torque value

%

- 200.00–200.00

0.01

R

6

2056

M08

Torque current

%

- 200.00–200.00

0.01

R

6

2057

M09

Output frequency

Hz

0.00–400.00

0.01

R

5

2058

M10

Motor output (input
electric power)

%

0.00–200.00

0.01

R

5

2059

M11

Output current r. m. s.

%

0.00–200.00 (inverter rating at
100.00)

0.01

R

5

2060

M12

Output voltage r. m. s.

V

0.0–600.0

1

R

3

2061

M13

Operation command (final
command)

-

Refer to data format [14]

-

R

14

2062

M14

Operating state

-

Refer to data format [16]

-

R

16

2063

M15

Universal output terminal
data

-

Refer to data format [15]

-

R

15

2064

M16

Fault memory 0

-

Refer to data format [10]

-

R

10

2065

M17

Fault memory 1

-

10

2066

M18

Fault memory 2

-

10

2067

M19

Fault memory 3

-

10

2068

M20

Integrated operating time

h

0–65535

1

R

1

2069

M21

DC link voltage

V

0–1000

1

R

1

2071

M23

Type code

-

Refer to data format [17]

-

R

17

2072

M24

Drive capacity code

-

Refer to data format [11]

-

R

11

2073

M25

ROM version

-

0–64999

1

R

1

2074

M26

Transmission error
processing code

-

Refer to data format [20]

-

R

20

2075

M27

Frequency command at
alarm (final command)

-

- 20000–20000 (max. frequency
at ±20000 )

1

R

2

2079

M31

Frequency command at
alarm (final command)

Hz

0–400.00 0.01

R

5

2080

M32

Actual frequency at alarm

-

- 20000–20000

1

R

2

(max. frequency a t ± 20000)

2081

M33

Actual torque at alarm

%

- 200.00 – 200.00

0.01

R

6

2082

M34

Torque current at alarm

%

- 200.00 – 200.00

0.01

R

6

2083

M35

Output frequency at alarm

Hz

0.00 – 400.

0.01

R

5

2084

M36

Motor output at alarm
(input power)

%

0.00–200.00

0.01

R

5

2085

M37

Output current r.m.s. at
alarm

%

0.00 – 200.00 (inverter rating at
100.00)

0.01

R

5

2086

M38

Output voltage effective
value at alarm

V

0.0 – 600.0

1

R

3

2087

M39

Operation command at
alarm

-

Refer to data format [14]

-

R

14

2088

M40

Operating state at alarm

-

Refer to data format [16]

-

R

16

2089

M41

Universal output terminal
data at alarm

-

Refer to data format [15]

-

R

15

2090

M42

Integrated operation time
at alarm

h

0–65535

1

R

1

2091

M43

DC link voltage at alarm

V

0–1000

1

R

1

2092

M44

Inverter internal air temp.
at alarm

°C

0–120

1

R

1

2093

M45

Cooling fin temp. at alarm

°C

0–120

1

R

1

2094

M46

Life of main circuit
capacitor.

%

0.0–100.0

0.1

R

3

2095

M47

Life of printed circuit
board capacitor.

h

0–65535

1

R

1

2096

M48

Life of cooling fan.

h

0–65535

1

R

1

Advertising