(1) Analog input terminals (13, 12, C1, and 11)
1.

These terminals receive low level analog signals that
may be affected by external noise. The cables must
be as short as possible (20 meters or less), must be
shielded, and the shields must be grounded. If the
cables are affected by external induction noise, the
shielding effect may be improved by connecting the
shield to terminal [11].

2.

If contacts must be connected to these circuits, twin
(bifurcated) contacts for handling low level signals
must be used. A contact must not be connected to
terminal [11].

3.

If an external analog signal output device is con-
nected to these terminals, it may malfunction as a
result of drive noise. To prevent malfunction, connect
a ferrite core or capacitor to the external analog
signal output device.

Item

min. typ.

max.

Operating voltage

ON

1V

2V

OFF

24V

27V

Maximum load current

ON

50 mA

Leakage current

OFF

0.1 mA

Fig. 2-3-10 Example of Noise Prevention

VR

1k to
5K ohms

Drive

13

12

11

Shielded wires

Fig. 2-3-9

Transistor

Y1

Transistor output 1

A running signal, frequency equivalence signal, overload early
warning output signal, and other signals from the drive are output
(as transistor output) to arbitrary ports. For details, see "Setting the
Terminal Functions E20 to E23" in Section 5.2 Function Explanation.
* <Specifications of transistor output circuit>

Y2

Transistor output 2

Y3

Transistor output 3

Y4

Transistor output 4

CMY

Transistor output common

Common terminal for transistor output signals. This terminal is
insulated from terminals (CM) and [11].

Relay output

30A,30B,30C

Alarm outputs for any fault.

If the drive is stopped by an alarm (protective function), the alarm
signal is output from the relay contact output terminal (1SPDT).
Contact rating: 250 VAC, 0.3A,cosØ = 0.3, 48 VDC, 0.5A for CE
Marking
An excitation mode (excitation at alarm occurrence or at normal
operation) can be selected.

Y5A,Y5C

Multi-purpose signal

These signals can be output similar to the Y1 to Y4 signals above.
The contact rating is the same as that of the alarm output above.

Communic-

DX+,DX–

RTU communication

Input / output signal terminals for RTU communication input / output

ation

Up to 31 inverters can be connected using the daisy chain method.

SD

Communication cable

Terminal for connecting the cable shield. The terminal is electrically

shield connection terminal

floating.-