Burkert Type 8681 User Manual

Page 32

Advertising
background image

32

24 V DC - Design

solenoid valves:
Power input per solenoid valve: max. 0.8 W (0.9 W during activation)
Power consumption per solenoid valve: 67 mA at 12 V DC

34 mA at 24 V DC

29 mA at 28 V DC

Operating mode:

Long-term operation (100 % ED)

central display of the switching states: 42 mA with a power supply of 24 V DC per illuminated display;

Color switching see chapter

16. LED - Color Assignments

Outputs/binary feedback signals: S1 out - S4 out
Design:

Normally open contact, PNP output

short-circuit-proof,

with self-clocking short-circuit protection

Switchable output current:

max. 100 mA per feedback signal

Output voltage - active:

≥ (operating voltage - 2 V)

Output voltage - inactive:

max. 1 V in unloaded state

Output/analog s3 out feedback signal (separate order variant "analog"!):
Signal output:

S3 out (binary feedback signal S3out not available)

Type:

Current source (4 to 20 mA)

Max. burden:

≤ 500 Ohm

Max. fault:

±1 mm (incl. measurement fault by the position measuring system)

input / proximity switches (external initiator: s4 in):
Power supply:

Voltage present at control head - 10 %

Current carrying capacity, sensor power supply: max. 90 mA
Short-circuit protection
Design:

DC 2- and 3-conductor,

NO or NC (factory setting NO), PNP output

Input current 1 signal:

I

Sensor

> 6.5 mA, limited internally to 10 mA

Input voltage 1 signal:

U

Sensor

> 10 V

Input current 0 signal:

I

Sensor

< 4 mA

Input voltage 0 signal:

U

Sensor

< 5 V

Valve control inputs (y1 - y3):
Signal level - active:

U > 10 V, max. 24 V DC + 10 %

Signal level - inactive:

U < 5 V

Impedance:

> 30 kOhm

english

Control Head Type 8681