Replacement of Components and Modules

Loosen the electronics module's fastening screw (Torx 10) (see chapter

19.2. Changing the Electronics

Module).

Tilt the electronics forwards to loosen the position measuring system's contact pins from the electronics module.

Bend the snap-fit hooks on the bottom end of the position measuring system inwards. In some cases, break

them off.

Pull the position measuring system upwards out of the guide.

installation procedure:

Insert the new position measuring from above so that the contact pins are located on the side of the elec-

tronics module.

Carefully push the housing of the position measuring system downwards until the snap-fit hooks snap into

place.

Slide the electronics module carefully onto the contacts pins and fasten the electronics module using the Torx

screw.

Remount the control head on the process valve as described in chapter

7. Installation.

Adjust position measuring system to the process valve by teaching (see chapter

15.1. Setting the Position

Measuring System (Teach-In))

Close the housing observing the notes contained in chapter "

8. Opening and Closing the Housing".