State of bus status led "network – Burkert Type 8681 User Manual

Page 59

Advertising
background image

59

DeviceNet - Design

state of bus status led "network"

12.13.2.

led

device state

explanation

troubleshooting

Off

No voltage / not
online

Device is not supplied with voltage

Device has still not ended Duplicate

MAC ID Test (test lasts approx. 2 s)

Device cannot end Duplicate MAC

ID Test.

Connect other devices, if the device

is the only network subscriber,

Replace device

Check baud rate

Check bus connection

Green

Online, connection
to master exists

Normal operating state with estab-

lished connection to the master

Flashes
green

Online, without
connection to
master

Normal operating state without

established connection to the
master

Flashes
red

Connection
time-out

One or more I/O connections are in

Time-Out state

New connection establishment by

master to ensure that the I/O data
is transmitted cyclically.

Red

Critical fault

Another device with the same MAC

ID address is in the circuit

No bus connection due to communi-

cation problems

Check baud rate

As a possible remedy of error,

please check address

If required, replace device

english

Control Head Type 8681