24 V DC - Design

design aid

10.3.

power consumption of the electronics:

P

El

= 0.7 W

or

I

El

= 30 mA at 24 V

power consumption of a valve during activation (200 ms):

P

Valve-On

= 0.9 W

or

I

Valve-On

= 38 mA at 24 V

power consumption of a valve after reduction:

P

Valve

= 0.8 W

or

I

Valve

= 34 mA at 24 V

power consumption of an optical position report:

P

LED

= 1.0 W

or

I

LED

= 42 mA at 24 V

Also, if several control head valves were to be opened simultaneously, the switch signal will be sent stag-
gered to the valves. Only

one valve will consume 0.9 W at any time.

Calculation examples:

example 1:
3 valves are activated simultaneously, one position is reported (state for 200 ms):

P

Total

=

P

El

+ 1 x P

Valve-On

+ 2 x P

Valve

+ 1 x P

LED

4,2 W =

0.7 W

+ 1 x 0.9 W

+ 2 x 0.8 W

+ 1 x 1.0 W

or

I

Total

=

I

El

+ 1 x I

Valve-On

+ 2 x I

Valve

+ 1 x I

LED

178 mA =

30 mA

+ 1 x 38 mA

+ 2 x 34 mA

+ 1 x 42 mA

example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):

P

Total

=

P

El

+ 3 x P

Valve

+ 1 x P

LED

4.1 W =

0.7 W

+ 3 x 0.8 W

+ 1 x 1.0 W

or

I

Total

=

I

El

+ 3 x I

Valve

+ 1 x I

LED

174 mA =

30 mA

+ 3 x 34 mA

+ 1 x 42 mA

When using an external initiator, its power requirement should be added.