Design aid, Design aid 11.5 – Burkert Type 8681 User Manual

Page 42

Advertising
background image

42

AS Interface - Design

NOTE!

if all three solenoid valves are simultaneously controlled via the as interface, the electronics will
activate the valves sequentially with a 200 ms time delay to protect the as interface from overloads.

Please observe the notes on power requirement and maximum expansion stage of the AS interface
network contained in chapter

11.3. Number of Connectable Control Heads and Maximum Length of the

Bus Line and in the AS Interface Specifications, where applicable.

external Power Supply:

External power supply

19.2 V DC to 31.6 V DC

The power supply unit must include a secure disconnect in accordance
with IEC 364-4-41. It must conform to the SELV standard. The ground
potential may not have an earth connection.

Max. power consumption from external

power supply for
outputs (solenoid valves) -
without integrated current limiting ≤ 110 mA at 24 V DC

Max. power consumption from AS interface

for inputs and display

≤ 150 mA typ.

Integrated short-circuit protection

Please observe the notes on power requirement and maximum expansion stage of the AS interface
network contained in chapter

11.3. Number of Connectable Control Heads and Maximum Length of the

Bus Line and in the AS Interface Specifications, where applicable.

design aid

11.5.

Design aid for supply of the valves via the AS Interface Bus

power consumption of the electronics:

P

El

= 1.0 W

or

I

El

= 33 mA at 30.5 V

power consumption of a valve during activation (200 ms):

P

Valve-On

= 0.9 W

or

I

Valve-On

= 30 mA at 30.5 V

power consumption of a valve after reduction:

P

Valve

= 0.8 W

or

I

Valve

= 26 mA at 30.5 V

power consumption of an optical position report:

P

LED

= 1.0 W

or

I

LED

= 33 mA at 30.5 V

For the design of the maximum line length observe chapter

11.3. Number of Connectable Control Heads and

Maximum Length of the Bus Line.

Also, if several control head valves were to be opened simultaneously via the bus, the switch signal will be
sent staggered to the valves. Only

one valve will consume 0.9 W at any time.

english

Control Head Type 8681