Burkert Type 8681 User Manual

Page 80

Advertising
background image

80

Maintenance, Troubleshooting

fault description

possible cause of the fault

troubleshooting

Feedback signal is lost in
system operation

Position in the limit range of the
feedback area

Repeat the Teach-In process
(see chapter

15.1. Setting the Position

Measuring System (Teach-In))
Check the process valve end positions
during operation against the end posi-
tions in non-operative state of the system.
Check the compressed air supply.

Valve output 2/A1 cannot be
switched off with the control

Magnetic manual control is still
activated

Deactivate the manual control -
see chapter "

17.1. Magnetic Manual

Control"

Valve outputs cannot be
switched off by the control

Mechanical manual control at the
solenoid valve is still activated

Deactivate the manual controls at the
solenoid valves -
see chapter "

17.2. Mechanical Manual

Control"

Faults are signaled by means
of LEDs

Possible causes may vary
depending on the version

Please read the corresponding descrip-
tions of the respective communication
variant in these operating instructions.

No or faulty function of the
process valves

No electrical power supply or com-
munication for the control head

Check the power supply and the com-
munication settings (also refer to detailed
descriptions of the respective versions in
these operating instructions)

No or insufficient pneumatic supply
of the control head

Check the compressed air supply and
ensure that supply is sufficient

Incorrect function of the
process valves

Confused pneumatic connection
lines

Check the correct pneumatic connection
of the control head to the process valve
(for Fluid Diagram, see chapter
"

5.4.2. Fluid diagram" and the operating

instructions of the corresponding process
valves)

Valves not correctly connected on
electronics module

Check the correct electrical connection
of the solenoid valves -
see

Fig. 11: 24 V DC electronics

module

In the event of any undefined faults, be sure to contact the service department of Bürkert.