Network topology of a devicenet system, Configuring the devicenet address / baud rate, Network topology of a devicenet system 12.9 – Burkert Type 8681 User Manual

Page 53

Advertising
background image

53

DeviceNet - Design

network Topology of a devicenet system

12.9.

When installing a DeviceNet system, ensure that the terminating circuit of the data lines is correct. The circuit pre-
vents the occurrence of interference caused by signals reflected onto the data lines.

The trunk line must be terminated at both ends with resistors of 120Ω and 1/4 W power loss (see "

Fig. 21:

Network topology").
Fig. 21: illustrates a line with one trunk line and several drop lines. T
runk lines and drop lines consist of identical
material.

Trunk line
DeviceNet cable

Terminating
resistor
120 Ω
¼ W

Terminating
resistor
120 Ω
¼ W

Drop lines
DeviceNet cable,
max. 6 m long

t01

tn

Subscriber 1 (node 1)

Subscriber n (node n)

V +
V –

CAN_H

CAN_L

Network topology

Fig. 21:

Configuring the devicenet address / baud rate

12.10.

8 DIP switches are available for configuration:

DIP switches 1 to 6

for the DeviceNet address

DIP switches 7 to 8

for the baud rate

Position of the DIP switches

Fig. 22:

english

Control Head Type 8681