Design aid, Design aid 13.3 – Burkert Type 8681 User Manual

Page 62

Advertising
background image

62

120 V AC - Design

design aid

13.3.

power consumption of the electronics:

P

El

= 1.2 VA

or

I

El

= 10 mA at 120 VA

power consumption of a valve during activation (200 ms):

P

Valve-ON

= 1.7 VA

or

I

Valve-ON

= 14 mA at 120 VA

power consumption of a valve after reduction:

P

Valve

= 1.4 VA

or

I

Valve

= 12 mA at 120 VA

power consumption of an optical position report:

P

LED

= 1.6 VA

or

I

LED

= 13 mA at 120 VA

Also, if several control head valves were to be opened simultaneously, the switch signal will be sent stag-
gered to the valves. Only

one valve 1.7 VA will ever be recorded.

Calculation examples:

example 1:
3 valves are activated simultaneously, one position is reported (state for 200 ms):

P

Total

=

P

El

+ 1 x P

Valve-ON

+ 2 x P

Valve

+ 1 x P

LED

7.3 VA =

1.2 VA

+ 1 x 1.7 VA

+ 2 x 1.4 VA

+ 1 x 1.6 VA

or

I

Total

=

I

El

+ 1 x I

Valve-ON

+ 2 x I

Valve

+ 1 x I

LED

61 mA =

10 mA

+ 1 x 14 mA

+ 2 x 12 mA

+ 1 x 13 mA

example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):

P

Total

=

P

El

+ 3 x P

Valve

+ 1 x P

LED

7.0 VA =

1.2 VA

+ 3 x 1.4 VA

+ 1 x 1.6 VA

or

I

Total

=

I

El

+ 3 x I

Valve

+ 1 x I

LED

59 mA =

10 mA

+ 3 x 12 mA

+ 1 x 13 mA

When using an external initiator, its power requirement should be added.

english

Control Head Type 8681