DeviceNet - Design

The addresses listed in the table above ("Static input assemblies") can be used as a path data for the attribute
Produced Connection Path of an I/O connection.

Nevertheless, by using this address data, the attributes combined in the assemblies can also be accessed acycli-
cally via Explicit Messages.

static Output assembly

12.11.2.

name

address of data attribute of the
assemblies for read access.
class, instance, attributes

format of the data attribute
Value 0: Off,
Value 1: On

Solenoid valves 1-3

4, 21, 3

Byte 0:

Bit 0: SV1

Bit 1: MV2

Bit 2: MV3

Bits 3-7: not used

The address listed in the table above ("Static input assembly") can be used as a path data for the attribute Pro-
duced Connection Path of an I/O connection.

Nevertheless, by using this address data, the attributes combined in the assemblies can also be accessed acycli-
cally via Explicit Messages.

Configuration of the device

12.12.

Configuration of the safety position of solenoid Valves if

12.12.1.

Bus error

The valve safety position and safety module attributes can be used to configure the solenoid valves in the event of
a bus error.

If a bus error occurs, the configuration data of the solenoid valves can be accessed acyclically via Explicit
Messages.

The

Get_Attribute_Single service stands for a read access of the configuration data.

The

Set_Attribute_Single service stands for a write access of the configuration data.

1 data byte for safety mode:
(Attribute address:
class 150, instance 1, attribute 7)

1 data byte for valve safety mode:
(Attribute address:
class 150, instance 1, attribute 6)

Bit

Mode

Value assignment

Bit

solenoid valve

Value assignment

Bit 0

Character-
istics in event
of bus error

0 Drive to
safety position
1 Retain last valve
position

Bit 0

Y1 (solenoid valve 1) Value 0: OFF / value 1: ON

Bit 1

Y2 (solenoid valve 2) Value 0: OFF / value 1: ON

Bits
1-7

not used

0 (always)

Bit 2

Y3 (solenoid valve 3) Value 0: OFF / value 1: ON

Bits
3-7

not used

0 (always)