Autotune functions, Autotune sequence, Autotune functions 15.2.2 – Burkert Type 8681 User Manual

Page 69: Autotune sequence 15.2.3

Advertising
background image

69

Position Measuring System

autotune functions

15.2.2.

teach-in

button

Mode

activa-

tion

duration

opt. feed-

back

teach-in

button

Function

activation

duration

opt. feed-

back

T2 + T3

Autotune

mode

2.5s

green +

yellow +

red

continuously

on

+

T1

Autotune 1

0.5s

green +

yellow +

red

chaser mode

T2

Autotune 2

T3

Autotune 3

T1 + T2

Autotune 4

T1 + T3

Autotune 5

T2 + T3

Autotune 6

The Autotune function can be selected after changing to Autotune mode. If an Autotune function has not been
started 10 seconds after the change to Autotune mode, that mode will be exited.

If an Autotune function is not working properly or is aborted (in case no compressed air is connected, for
example), the already taught positions are deleted again; the corresponding Autotune function is exited
and switched to normal operation.
The teach positions are set to "not taught", i.e. they blink in the fault color.

autotune sequence

15.2.3.

autotune 1:

control

effect on the process valve

internal program

error

t2 + t3

autotune mode starts

t1

Autotune 1 starts

Closed position

Teach

T1

Valve opens

Activate

V1

Wait period

10s

Open position

Teach

T2

Valve closing

Deactivate

V1

Valve closes

Wait on position S1

S1

Timeout 15s

autotune mode completed

example illustration of the autotune procedure 1:

1. Check in what position the process valve must be at the beginning of the Autotune procedure (here: closed
position). Close it if necessary.

2. Press the teach buttons T2 and T3 at the same time (for 2.5 s) to select the Autotune mode.
This mode will be indicated by continuous illumination of all 6 LEDs.

3. Press teach button T1 (for 0.5 s) to start the Autotune 1 mode. This will be indicated by
illumination of all 6 LEDs in "chaser mode". Only the programmed sequence
for "Auto-Teach sequence" 1 will run fully automatically:

- The position in that the process valve is adjusted will be taught first as position S1.
The position of the process valve must therefore be checked first!
- After that, valve V1 is activated. It initiates opening of the process valve.
- After maximum 10 s, the process valve has reached position S2 (open position).

english

Control Head Type 8681