Burkert Type 8681 User Manual

Page 41

Advertising
background image

41

AS Interface - Design

connections:

Multi-pole connection version

1 x M16 x 1.5 cable gland / A/F19 with multi-pole connection

(M12 plug according to IEC 61076-2-101, 4-pole on a cable of 8 or
80 cm length for power supply and signal)

1 x M16 x 1.5 cable gland / A/F19

for external initiator
clamping area 3 to 6 mm, with dummy plugs
with screw terminals for cable cross-sections 0.14 to 1.5 mm²

power supply:

29.5 to 31.6 V DC (according to specification)

input / proximity switches (external initiator: s4 in):
Power supply:

AS interface voltage present at control head - 10 %

Current carrying capacity, sensor
power supply:

max. 30 mA

Short-circuit protection
Design:

DC 2- and 3-conductor,

NO or NC (factory setting NO), PNP output

Input current 1 signal:

I

Sensor

> 6.5 mA, limited internally to 10 mA

Input voltage 1 signal:

U

Sensor

> 10 V

Input current 0 signal:

I

Sensor

< 4 mA

Input voltage 0 signal:

U

Sensor

< 5 V

inputs (from master perspective) binary feedback signals:
The retrieval of the 3 valve positions reported back binarily is described in chapter

15. Position Measuring System.

Outputs (from master perspective) / solenoid valves:

Switcing capacity, max.

0.8 W via AS interface or 0.9 W during activation, per solenoid valve

Watchdog function

integrated

Output power reduction

via AS interface - electronics integrated

pull-in current

30 mA or 0.9 W / 200 ms (at 30.5 V AS Interface voltage)

Holding current

26 mA or 0.8 W

(at 30.5 V AS Interface voltage)

Operating mode

Long-term operation (100 % ED)

Valve type

Type 6524

Central display of the switching states:

power consumption from AS-i

at 30.5V AS Interface voltage

max. 33 mA or 1 W per illuminated display

Number of representable colors 2 colors for process valve switching states

1 color for signaling a fault
For "universal color switching", see chapter

16. LED - Color

Assignments.

Power supply via aS interface bus (without external power supply):

Max. power consumption from AS interface

200 mA (incl. external initiator with 30 mA)

Power consumption input during normal operation

from the AS interface (after current reduction):

≤ 150 mA

3 valves activated, 1 Position reported back by LED
display, no external initiator

Integrated short-circuit protection

english

Control Head Type 8681

Advertising