Setting the baud rate, Configuration of process data, Static input assemblies – Burkert Type 8681 User Manual

Page 55: Configuration of process data 12.11

Advertising
background image

55

DeviceNet - Design

setting the baud rate

12.10.2.

Adjustment of the control head to the baud rate of the network.

Baud rate

dip 7

dip 8

125 kbaud

off

off

250 kbaud

on

off

500 kbaud

off

on

not permitted:

(on)

(on)

if the settings are changed by actuating the dip switches, this change will not take effect until the
device is restarted.
For a restart

briefly disconnect the control head from the power supply and reconnect or

switch the power supply off/on or

transmit an appropriate reset message.

Configuration of process data

12.11.

To transmit process data via an I/O connection, 2 static input and 1 static output assembly can be selected.
These assemblies contain selected attributes combined into one object so that process data can be transmitted
collectively via an I/O connection.

The process data is selected by setting the device parameters Active Input Assembly and Active Output Assembly
or - if supported by the DeviceNet-Master/Scanner - by setting Produced Connection Path and Consumed Con-
nection Path when an I/O connection is initialized according to the DeviceNet specification.

static input assemblies

12.11.1.

name

address of data attribute of the
assemblies for read access.
class, instance, attributes

format of the data attribute
Value 0: Off
Value 1: On

S1 - S4 (factory setting)

4, 1, 3

Byte 0:
Bit 0: Position S1

Bit 1: Position S2

Bit 2: Position S3

Bit 3: Position S4

S1 - S4 + POS

(with POS:
actual position)

4, 2, 3

Byte 0:
Bit 0: Position S1

Bit 1: Position S2

Bit 2: Position S3

Bit 3: Position S4

Bits 4-7: not used

Byte 1:
POS in mm

english