Changing the position measuring system, Changing the position measuring system 19.4 – Burkert Type 8681 User Manual

Page 84

Advertising
background image

84

Replacement of Components and Modules

Loosen the electrical connections.

Loosen the connecting screws (Torx T10) for the corresponding valve module.

Take out the valve module and replace it with the spare part set.

When inserting the valve module, make sure that the form seal fits correctly and fully on the lower side of the

respective valve flange!

Valve module: For this, insert the screws (Torx T10) in the existing threading by turning them backwards and

tighten them with a torque of 1.2 Nm.

Reattach the electrical connections.

(If other connections apart from the solenoid valve connections have been removed, read the corresponding
chapters on the electrical installation of the respective voltage / bus / connection version).

Close the housing observing the notes contained in chapter "

8. Opening and Closing the Housing".

Changing the position Measuring system

19.4.

The position measuring system consists of a housing, with a PCB mounted above with LEDs and light conductor.
There are four snap-fit hooks with which the position measuring system is secured in the lower housing part by
snapping into place.

PCB with LEDs and light
conductor

Housing of the Position
Measuring System

Snap-fit hooks (4x)

Position Measuring System

Fig. 33:

english

Control Head Type 8681

Advertising