AS Interface - Design

electrical Connection Options for as interface

11.2.

The following connection concepts are available for the electrical connection of the control head:

Cable gland with multi-pole connection on a cable (8 cm length)

Cable gland with multi-pole connection on a cable (80 cm length)

with multi-pole connection

(M12 plug

according to IEC 61076-2-101, 4-pole)
on 8 cm cable

with multi-pole connection

(M12 plug according to

IEC 61076-2-101, 4-pole) on 80 cm cable

left: AS interface

right: external initiator

left: AS interface

right: external initiator

Connection Concepts for AS Interface

Fig. 14:

11.3. number of Connectable Control Heads and

Maximum length of the Bus line

The bus cable may be a maximum of 100 m long.

The level of expansion that is actually possible depends on the total number of all individual operating currents for each
control head, which are supplied via the bus at the common AS interface bus segment (see example calculation).

Default: aS interface / 62 slaves (aS interface version with extended addressing range (a/B slave))

In AS interface versions with extended addressing range (A/B slave), 1 master can communicate with 62 slaves.

option: aS interface / 31 slaves (aS interface version with 31 slave addressing range)

In this case, a maximum of 31 control heads can be connected to a bus line (the address range restriction).