68

Position Measuring System

If necessary, return control head and system to normal state (switching position, power supply).

Close the housing observing the notes contained in chapter

8. Opening and Closing the Housing.

If the piston or the target are located outside the measuring area during the teaching phase, the LED will
flash 3 times in the defined fault color.

If the piston or target are outside of the measuring area, no positions signals will report back, i.e. no LEDs
will be lit.

The Teach-In buttons can be assigned to any of the positions of the piston, i.e. T1 does not have to corre-
spond to the lower piston position, etc.

Teach-In buttons

T2

T3

T1

Electronics module, 24 V DC

Electronics module, ASI

Teach-In buttons on the electronics modules (on the example of the electronics modules for 24 V DC and AS-i)

Fig. 27:

Teach-in functions

15.2.

Teach-in functions and Teach-in reset

15.2.1.

teach-in

button

Function

activation

duration

optical feedback

T1

Teach function S1

1.5 s

S1 blinks quickly three times, then continuously in the encoded color

T2

Teach function S2

1.5 s

S2 blinks quickly three times, then continuously in the encoded color

T3

Teach function S3

1.5 s

S3 blinks quickly three times, then continuously in the encoded color

T1 + T2

Teach-In reset S1, S2,

and S3

2.5 s

Blinks in the fault color

Difference between the different "blinking patterns" - see chapter

16.2. Blinking Pattern & Fault Signaling.

english

Control Head Type 8681