DeviceNet - Design

Inputs

3 discrete feedback signal of the position measuring system (positions S1 - S3)
1 discrete feedback signal of the external initiator (S4)
1 analog position signal in mm
supply via DeviceNet string (11 to 25 V DC)
Switch level high signal ≥ 5 V
Switch level low signal ≤ 1.5 V

Outputs

3 solenoid valves

Power consumption
from the bus:

max. output 5 W, if all valves are switched (3 x type 6524 with 0.8 W each)

Total line length and maximum line length according to

12.3.1.

devicenet specification

The bus line is a 4-core cable with additional shielding which must conform to the DeviceNet specification. The cable
transmits both information (data) and energy (power supply for low-power actuators and sensors).

The maximum total line length (sum of trunk lines and drop lines) of a network depends on the baud rate.

Baud rate

Maximum total line length*

1

thick cable*

2

thin cable*

2

125 kbaud

500 m

100 m for all baud rates

250 kbaud

250 m

500 kbaud

100 m

*

1

A

ccording to DeviceNet specification. If a different cable type is used, lower maximum values apply.

*

2

For cable designation and details refer to DeviceNet specification

drop line length

12.3.2.

Baud rate

length of the drop lines

Maximum length

Maximum total length of all drop lines in the
network

125 kbaud

6 m for all baud rates

156 m

250 kbaud

78 m

500 kbaud

39 m

english