DeviceNet - Design

electrical data

12.4.

connections:

"Multi-pole"

1 x M16 x 1.5 cable gland / SW22 with multi-pole connection

(M12 plug according to IEC 61076-2-101, 5-pole on a cable of 80 cm
length ) for DeviceNet bus and power supply

1 x M16 x 1.5 cable gland / SW19 for external initiator

clamping area 3 to6 mm, with dummy plugs
with screw terminals for cable cross-sections 0.14 to 1.5 mm²

electrical power supply:

11 to 25 V DC (according to specification)

Max. power consumption:

200 mA at 24 V DC

input / proximity switches (external initiator: s4 in):
Power supply:

via DeviceNet power supply - 10 %

Current carrying capacity sensor
power supply:

max. 30 mA

Short-circuit protection
Design:

DC 2- and 3-conductor,

Normally open contact, PNP output

Input current 1 signal:

I

Sensor

> 6.5 mA, limited internally to 10 mA

Input voltage 1 signal:

U

Sensor

> 10 V

Input current 0 signal:

I

Sensor

< 4 mA

Input voltage 0 signal:

U

sensor

< 5 V

inputs (from master perspective) / binary or analog feedback signals:
The recovery of the 3 valve positions reported back binarily or of the analog position signalis described in
chapter

15. Position Measuring System.

Outputs (from master perspective) / solenoid valves:
max. switching capacity

1.0 W

typ. continuous output

0.8 W

Output reduction

via DeviceNet interface - electronics integrated

pull-in current

120 mA typ. / 200 ms (3 valves)

Holding current

100 mA typ. at 24 V DC (3 valves)

Operating mode

Long-term operation (100 % ED)

Valve types

6524

central display of the switching states:

Power consumption from DeviceNet

at 24 V DC

42 mA with 24 V DC power supply per illuminated display shown;

Color switching see chapter

16. LED - Color Assignments

safety position if the Bus fails

12.5.

If the bus fails, the solenoid valve is switched to a programmable safety position (default: solenoid valve is in power-
off-state). For configuration data see chapter "

12.12.1. Configuration of the Safety Position of Solenoid Valves if

Bus Error".