Programming data, Hapter, Programming – Burkert Type 8681 User Manual

Page 46: Data

Advertising
background image

46

AS Interface - Design

11.8. programming data

The control heads have been configured as AS interface version with an extended address range (A/B slaves) for
62 slaves or optionally as an AS interface version for 31 slaves.

A change between the two configurations in the control head is only possibly by exchanging the elec-
tronic PCB!

If one control head is replaced with another control head having a different configuration in the AS interface
field bus system (e.g. AS interface version 62 slaves (A/B-Slave) to replace a device with AS interface version
31 slaves), a configuration error will be generated at the master due to the different ID codes!

In this case (intentional replacement), the current configuration must be reprojected in the AS interface
master. Please read the operating instructions of the used AS interface master!

programming data table:

programming data for 62 slaves
as interface - device for a/B slave
addressing (default device)

programming data for 31 slaves
as interface (optional)

I/O configuration

7 hex (4 inputs / 4 outputs)

See the

Bit Configuration Table:

7 hex (4 inputs / 4 outputs)

See the

Bit Configuration Table:

ID code

A hex

F hex

Extended ID code 1

7 hex

(F hex)

Extended ID code 2

E hex

(F hex)

Profile

S-7. A.E

S-7. F.F

Bit configuration table:

data bit

d3

d2

d1

d0

Input

External initiator S4

Position 3

Position 2

Position 1

Output

not used

Solenoid valve 3

Solenoid valve 2

Solenoid valve 1

parameter bit

p3

p2

p1

p0

Output

not used

not used

not used

not used