Signal priorities – Burkert Type 8681 User Manual

Page 74

Advertising
background image

74

LED - Color Assignments

Blinking patterns

on

oFF

note

250 ms

250 ms

permanent blinking in the fault color:
- Teaching does not occur

or

- Teach-Reset has been performed or
- Bus error
permanent blinking in the color for that position:
Signal from position 3

450 ms

50 ms

Internal Fault (fault color)

50 ms

450 ms

Service mode / manual control active
(fault color)

125 ms

125 ms

Signal from the external initiator S4
(like "color for position 3")

1 s

3 s

Signal in fault color (and additionally
color of the corresponding valve position):
Maintenance/service required

16.3. signal priorities

if a valve has several overlapping states, the following priority list applies:

Internal Fault (fault color: 450 ms ON, 50 ms OFF)

1.

Manual operating mode is active, e.g. by magnetic manual control - see chapter

2.

17. Service Mode / Manual

Control (fault color: 50 ms ON, 450 ms OFF)

Maintenance/service prompt (fault color: 1 s ON, 3 s OFF)

3.

Other fault, e.g. position measuring system not taught, bus error or other (see chapter

4.

16.2. Blinking Pattern

& Fault Signaling)

if position feedback signals overlap, the following logic applies:
ON principle, S4 has the highest priority, descending to S1 (i.e. S4 - S3 - S2 - S1).

s1

s2

s3

s4

fault

priority note / Blinking patterns

active

active

active

active

S4

Blinking in S4 blinking pattern (if S4 has been acti-
vated by DIP) since S3/S4 has priority over S1 and S2

active

active

S4

Blinking in S4 blinking pattern, if S4 has been acti-
vated by DIP

active

active

active

S3

Blinking in S3 blinking pattern since S3/S4 position
has priority over S1 and S2

active active

S2

Position feedback of S2 has priority

english

Control Head Type 8681