Position Measuring System

- Then position S2 is taught.
- After that, valve V1 is deactivated. It initiates closing of the process valve.
- Once the process valve is closed (after 15 s maximum), position S1 is displayed by LED.

4. Autotune sequence 1 is complete: positions S1 and S2 have been taught.

In the event that a timeout occurs, the corresponding Autotune function will be exited and switched to
normal operation.
Furthermore, the Teach-In positions will be set to "not taught", i.e. they will blink in the fault color.

autotune 2:

control

effect on the process valve

internal program

error

t2 + t3

autotune mode starts

t2

Autotune 2 starts

Open position

Teach

T2

Valve closing

Activate

V1

Wait period

10s

Closed position

Teach

T1

Valve opens

Deactivate

V1

Valve opens

Wait on position S2

S2

Timeout 15s

autotune mode completed

autotune 3:

control

effect on the process valve

internal program

error

t2 + t3

autotune mode starts

t3

Autotune 3 starts

Closed position

Teach

T1

Valve opens

Activate

V1

Wait period

10s

Open position

Teach

T2

Valve closing

Deactivate

V1

Valve closes

Wait on position S1

S1

Timeout 15s

Open clock valve plate

Activate

V2

Wait period

10s

Clock valve plate

Teach

T3

Valve closing

Deactivate

V2

Valve closes

Wait on position S1

S1

Timeout 15s

autotune mode completed

english

Control Head Type 8681