Installationandcommissioning

flow direction

50 x DN 5 x DN

40 x DN 5 x DN

25 x DN 5 x DN

20 x DN 5 x DN

18 x DN 5 x DN

15 x DN 5 x DN

With control valve

Pipe with 2 elbows at 90° in 3

dimensions

Pipe with 2 elbows at 90°

Pipe with 1 elbow at 90° or 1

T-piece

With pipe expansion

With pipe reduction

Fig. 7:

Upstream and downstream distances depending on the design of the pipes.

Respect the following additional mounting conditions to ensure that the measuring device operates correctly:

- Preferably install the device at a 45° angle to the horizontal centre of the pipe to avoid having deposits on the elec-

trodes and false measurements due to air bubbles (see “Fig. 8”);

45°

45°

Fig. 8:

Mounting angle on the pipe

- Ensure that the pipe is always filled in the section around the device (see Fig. 9).

- When mounting vertically ensure that the flow direction is in an upward direction (see Fig. 9).

Horizontal mounting

Correct

Incorrect

Vertical mounting

Correct

Incorrect

flow direction

Fig. 9:

Filling of the pipe

- Prevent the formation of air bubbles in the pipe in the section around the device (see Fig. 10).