Fig. 41, Output do2 directio. do3 inv yes inv no, Del. 2= 00 – Burkert Type 8045 User Manual

Page 49

Advertising
background image

45

Operatingandfunctions

When the measured flow rate is in the cut-off flow range (see chap. “8.6.16”), the flow rate is set to
0 and positive. The following diagram shows the behaviour of the DO output when it is configured to
indicate the fluid circulation changes, when the CUT-OFF function is used.

+CUTOFF

t

0

-CUTOFF

DEL

DEL

DO output active

DO output inactive

measured flow rate

displayed flow rate

flow rate

As long as the measured flow rate is lower than "-CUTOFF", the device status
LED is orange and the message "NEG. FLOW" is added to the warning message
list.

The DO2 or DO3 relay output can be configured to indicate the fluid circulation change.

OUtPUt

DO2

DiRECtiO.

DO3

iNV YEs

iNV NO

0......9

Choose the operating, inverted or not inverted, of the
relay output.

DEL. 2= 00

Enter the time delay before switching value (value
between 0 and 99 s).

Confirm.

Fig. 41:

Configuration of the DO2 or DO3 relay output to indicate the fluid circulation changes

English

Type 8045