8.6.6.
configuring the Ao1 current output
The current output gives a 22 mA current when the device shows an operation fault, even if the current
output is disabled.
The 4-20 mA output provides an electrical current, the value of which reflects the flow rate measured by the
device.
Example of relation between the measuring range and the current output:
4
20
20
180
mA
l/min
→
To invert the output signal, give a lower flow rate value to the 20 mA current value than to the 4 mA current
value.
→
To disable the current output, set both range bounds, 4 and 20 mA, to zero. In this case the output delivers a
constant current of 4 mA.
OUtPUt
4 = 28.00
AO1
DO1
→
Enter the flow rate associated to a 4 mA current value, in the unit
chosen in the "UNIT" parameter.
→
Confirm.
20 = 6.000
→
Enter the flow rate associated to a 20 mA current value, in the unit
chosen in the "UNIT" parameter.
→
Confirm.
Fig. 33:
Parameterizing the current output