Setting the kw coefficient of the flow sensor, Monitoring the flow rate in the pipe – Burkert Type 8045 User Manual

Page 61

Advertising
background image

57

Operatingandfunctions

FLOw

sim=12,50

Enter a flow rate value.

Confirm by pressing the

ENTER

key.

Check that the outputs are behaving as expected.

To test another value, press

ENTER

.

To exit the checking, press

or

0......9

.

Fig. 58:

Diagram of the "FLOW" parameter of the Test menu

If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press

ENTER

to save the settings or not and go back to the Process level.

8.7.4.

Setting the Kw coefficient of the flow sensor

This parameter makes it possible to adjust the accuracy of the device.

Modifying the Kw coefficient has consequences for determining the fitting K factor using a teach-in pro-
cedure. See chap. “8.6.4”.

K-sENsOR

Kw= 1.000

Enter the Kw coefficient of the flow sensor. Value between 0,850 and 1,150.

Confirm.

FLOw-w.

Setting example: to increase the measured flow rate value by 1,5 %, enter KW= 1,015.

Fig. 59:

Diagram of the "K-SEnSOR" parameter of the Test menu

If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press

ENTER

to save the settings or not and go back to the Process level.

8.7.5.

monitoring the flow rate in the pipe.

A malfunction in your process or the flow sensor may be indicated either by too low or too high a flow rate.

This parameter makes it possible to monitor the flow rate and configure the behaviour of the device if the param-
etered range is exceeded.

• To disable the flow rate monitoring, set W- = W+ = 0.

• To disable one of the limits, set it to 0.

English