Installationandcommissioning

Earth cable coming from the housing.

On a version with stainless steel flow sensor, a second cable

is coming from the sensor.

1 2 3 4 5 6

Fig. 19:

Terminal block 1 connecting the earth wire coming from the housing (made in the factory)

7.3.4.

Wiring the Ao1 current output

For safety reasons, secure the cables using a non-conducting cable clamp.

The 4-20 mA output can be wired in either sourcing or sinking mode.

Power supply

4-20mA input at external

device

Position the

A

switch to the right.

SOURCE

SINK

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

CURRENT

PE

AO1

A

18-36 V DC

+

-

300 mA

I

+

-

(*)

SOURCE

SINK

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

CURRENT

PE

AO1

A

18-36 V DC

+

-

300 mA

I

+

-

(*)

Power supply

4-20mA input at external

device

Position the

A

switch to the left.

Fig. 20:

Wiring of the 4-20 mA output (AO1) in
sourcing mode

Fig. 21:

Wiring of the 4-20 mA output (AO1) in sinking
mode

*) If a direct earth connection is not possible, fit a 100 nF/50 V capacitor between the negative power supply terminal and the
earth