Terminal assignement and use of the selectors, Source sink current source sink current, Off on – Burkert Type 8045 User Manual

Page 28

Advertising
background image

24

Installationandcommissioning

7.3.3.

Terminal assignement and use of the selectors

4 pin ribbon ca-

ble coming from

the flow sensor

SOURCE

SINK

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

CURRENT

PE

DI1

PE

DO2

DO3

AO1

+

-

OFF ON

2

B

1

4

5

3

A

Selector A : see Fig. 17
Selector B : see Fig. 18

terminal block 1
Iout: 4-20 mA output (AO1)
L+: V+ (positive voltage)
L-: 0V (power supply ground)
PE: functional earth, wired in the factory (see Fig.
19)
P+: positive transistor output (DO1)
P-: negative transistor output (DO1)

terminal block 2
PE: shieldings of both the power supply cable and
the AO1 and DO1 output cables

terminal block 3
PE: functional earth of the DI1 digital input
-: negative signal of the DI1 input
+: positive signal of the DI1 input

terminal block 4 wiring the DO2 relay output
terminal block 5 wiring the DO3 relay output

Fig. 16:

Terminal assignment

Use switch A to configure the wiring of the 4-20 mA current output in sinking or sourcing mode.

Wire the current output in sourcing mode.

Wire the current output in sinking mode.

A

SOURCE

SINK

CURRENT

SOURCE

SINK

CURRENT

Fig. 17:

Using the sink/source switch

Use the switch B to lock/unlock the

ENTER

key to prevent unauthorized access to the configuration of the

device.

The

ENTER

key is unlocked (default position).

The

ENTER

key is locked.

OFF ON

B

OFF ON

Fig. 18:

Using the EnTER key lock/unlock switch

English

Type 8045

Advertising