Configuring the do2 and do3 relay outputs, Emitted by the device, Fig. 39 – Burkert Type 8045 User Manual

Page 47

Advertising
background image

43

Operatingandfunctions

8.6.10. configuring the transistor output Do1 to switch a load

when a warning message is emitted by the device

When the device generates a warning message, the device status LED is orange.

The generation of a warning message can also be indicated by the switching of the transistor output.

REtURN

On a version WITH relay out-

puts

On a version WITHOUT relay

outputs

OUtPUt

DO1

wARNiNG

DO2

iNV YEs

iNV NO

0......9

Choose the operating, inverted or not inverted, of the
transistor output.

DEL. 1= 00

Enter the time delay before switching value (value
between 0 and 99 s).

Confirm.

Fig. 39:

Configuration of the DO1 transistor output to indicate the generation of a warning message

8.6.11. configuring the Do2 and Do3 relay outputs

Any DO relay output can be configured either:

• to switch a load depending on two thresholds. See “Fig. 36”, chap. “8.6.7” and “Fig. 40”.

• to switch a load to indicate the fluid circulation changes. See “Fig. 41”.

• to switch a load when a warning message is generated by the device. See “Fig. 42”.

English

Type 8045