Fig. 38, Return, Output do1 directio. do2 inv yes inv no – Burkert Type 8045 User Manual

Page 46: Del. 1= 00

Advertising
background image

42

Operatingandfunctions

8.6.9.

configuring the transistor output Do1 to switch a load
when the fluid direction changes

The DO1 transistor output can be configured to indicate the fluid circulation change.

When the measured flow rate is in the cut-off flow range (see chap. “8.6.16”), the flow rate is set to
0 and positive. The following diagram shows the behaviour of the DO output when it is configured to
indicate the fluid circulation changes, when the CUT-OFF function is used.

+CUTOFF

t

0

-CUTOFF

DEL

DEL

DO output active

DO output inactive

measured flow rate

displayed flow rate

flow rate

As long as the measured flow rate is lower than "-CUTOFF", the device status
LED is orange and the message "NEG. FLOW" is added to the warning message
list.

REtURN

On a version WITH relay out-

puts

On a version WITHOUT relay

outputs

OUtPUt

DO1

DiRECtiO.

DO2

iNV YEs

iNV NO

0......9

Choose the operating, inverted or not inverted, of the
transistor output.

DEL. 1= 00

Enter the time delay before switching value (value
between 0 and 99 s).

Confirm.

Fig. 38:

Configuration of the DO1 transistor output to indicate the fluid circulation changes

English

Type 8045