Fig. 46 – Burkert Type 8045 User Manual

Page 52

Advertising
background image

48

Operatingandfunctions

The preset flow rate is ignored if there is a running check for the correct behaviour of the outputs (see
chap. “8.7.3”).

This function makes it possible, like the Hold mode, to freeze the flow rate maesure, but to a preset value set by
the user.

When the digital input is activated:

• the device status LED flashes.

• the current transmitted on the 4-20 mA is frozen to the preset value of the flow rate.

• the displayed flow rate is frozen to the preset value of the flow rate.

• each transistor or relay output behaves depending on the preset flow rate.

• the totalizers do not increment any more.

• the preset flow rate is active until the digital input switches again.

iNPUt

Di1

sEt FLOw

REtURN

iNV YEs

iNV NO

0......9

Choose "INV. NO" to trigger the input on the leading
edge.

Choose "INV. NO" to trigger the input on the trailing
edge.

Confirm

sF= 0.000

Enter the flow rate value, in the unit chosen in the
"UNIT".parameter.

Confirm

Fig. 46:

Configuration of the digital input to trigger the status of the outputs depending on a preset flow rate