64

Maintenanceandtroubleshooting

9.5.3.

resolution of problems without message generation and
device status leD green

Device
status
leD

current
output
Ao1

output Do1
and/or Do2
and/or Do3

possible cause

recommended action

green

4-20 mA depending on

the thresholds or
switched

1)

he device does not properly
measure the flow rate.

Check that the K factor corre-
sponds to the fitting used.

Check that the Kw coefficient has
not been disturbed.

Carry out a teach-in procedure
to determine the K factor of the
fitting used.

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate is not
nil but the flow rate in the pipe
is.

Check that the flow rate in the
pipe is nil.

Check that there are no bubbles in
the pipe.

Check the filter chosen.

Calibrate the flow zero point.

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate is
always nil.

Check that the flow rate in the
pipe is not nil.

Check that the K factor or the Kw
coefficient are not too low.

Check that the electrodes are per-
pendicular to the flow direction.

Choose a smaller flow rate unit or
increase the number of displayed
decimals..

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate is not
stable.

Check that there is fluid in the pipe.

Choose a higher filter.

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate
changes very slowly.

Check that there is fluid in the pipe.

Choose a lower filter.

1)

If the output is configured to switch when a warning message is generated. See chap. 8.6.5.