Wiring the do1 transistor output, Wiring the di1 digital input, Wiring the do2 and do3 relay outputs – Burkert Type 8045 User Manual

Page 30: English, 26 installationandcommissioning, Fig. 25: wiring of the do2 and do3 relay outputs, Type 8045

Advertising
background image

26

Installationandcommissioning

7.3.5.

Wiring the Do1 transistor output

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

PE

AO1

300 mA

+

-

18-36 V DC

(*)

+

-

+

- 5-36 VDC

PLC

Power supply

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

PE

AO1

300 mA

(*)

+

-

+

- 5-36 VDC

+

-

18-36 V DC

Power supply

PLC

Fig. 22:

nPn wiring of the DO1 transistor output

Fig. 23:

PnP wiring of the DO1 transistor output

*) If a direct earth connection is not possible, fit a 100 nF/50 V capacitor between the negative power supply terminal and the
earth

7.3.6.

Wiring the DI1 digital input

SOURCE

SINK

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

CURRENT

PE

DI1

PE

DO2

DO3

AO1

+

-

18-36 V DC

+

-

(*)

Power supply

Switch

Power supply

Switch

SOURCE

SINK

L+ L- PE P+ P-

Iout

Supply

18...36 Vdc

PULSE

DO1

CURRENT

PE

DI1

PE

DO2

DO3

AO1

+

-

18-36 V DC

+

-

(*)

Fig. 24:

Possible wirings of the DI1 digital input

*) If a direct earth connection is not possible, fit a 100 nF/50 V capacitor between the negative power supply terminal and the
earth

7.3.7.

Wiring the Do2 and Do3 relay outputs

DO2

DO3

230 VAC

m

3 A

3 A

230 VAC

Fig. 25:

Wiring of the DO2 and DO3 relay outputs

English

Type 8045