Linear 0-10vdc input example, Linear 4-20ma input example, Linear 4-20ma input example 101 – Watlow PPC-2000 User Manual
Page 125
PPC-2000 User’s Guide
Chapter 3: Operating with AnaWin 3
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
101
Linear 0-10Vdc Input Example
For a sensor that measures pressures from 0.0 to 15.0 psia and
outputs a 0-10Vdc signal, set the following parameters:
Table 3.5
Scaling Parameters for 0-10Vdc
Linear Input Example
Linear 4-20mA Input Example
For a sensor that measures relative humidity with a range of
0.00 to 100.00% and outputs a 4-20mA signal, set the
parameters according to Table 3.6.
Table 3.6
Scaling Parameters for 4-20mA Linear
Input Example
Parameter
Setting
Units
Input Type
Linear -1 to 10 (v)
Units
psia
Input Signal Lo
0.000
V
Input Signal Hi
10.000
V
PV Lo
0.0
psia
PV Hi
15.0
psia
Decimal Places
1
Parameter
Setting
Units
Input Type
Linear -2 to 20 (mA)
Units
%
Input Signal Lo
4.000
mA
Input Signal Hi
20.000
mA
PV Lo
0.00
%
PV Hi
100.00
%
Decimal Places
2