PPC-2000 User’s Guide

Chapter 2: Hardware Installation

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

51

Figure 2.33 Wiring 2-Wire RTDs: Input 1 and 2

Shown

Three-wire RTDs may only be used with differential analog
input modules. The single wire side of a 3-wire RTD sensor
connects to the

COM

terminal, one of the double wire sides

connects to the

A

terminal and the other connects to the

B

terminal. Both

A

and

B

terminals must be of the same desired

input, i.e.,

1A

and

1B

. See Figure 2.34.

Figure 2.34 Wiring 3-Wire RTDs: Input 1 and 2

Shown

1A (input 1+)

1B (input 1-)

COM

2A (input 2+)

2B (input 2-)

AITB

1A (input 1+)

COM

2A (input 2+)

2B (input 2-)

1B (input 1-)

AITB

A

B

COM

Advertising