Processor module leds, Processor module leds 147 – Watlow PPC-2000 User Manual

Page 173

Advertising
background image

PPC-2000 User’s Guide

Chapter 4: Troubleshooting

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

147

15. Reset the controller and download the AnaWin3 Snapshot.

Refer to Resetting Closed-Loop Control Parameters on
page 156.

16. Reload logic program stored variables.

Processor Module LEDs

Refer to the following descriptions of LED indicators when
troubleshooting the Processor module.

Status Green LED On: Normal condition with logic
program stopped.

Status Green LED blinking four times per second,
on briefly (230 ms Off, 20 ms On):
Normal condition
with logic program running.

Status LED Off: Indicates low power input.

Corrective Actions:

Check power connections.

Measure power output from power supply.

Disconnect I/O to check for excessive draw on power
supply.

Status Green LED blinking four times per second,
off briefly (50 ms Off, 200 ms On):
Seen at the
beginning of logic program download while previous logic
program is being erased.

Error 1 Orange LED and Error 2 Red LED on:
Indicates watchdog timeout — control program no longer
running.

Corrective Actions:

Cycle power to PPC-2000 system. Perform RAM clear; see
Resetting Closed-Loop Control Parameters on page 156.

Replace Processor module.

Error 1 Orange LED on: Indicates low battery or low
voltage from the power supply.

Corrective Actions:

Check to make sure the voltage on the power supply is 12
to 28Vdc.

Replace the battery. See Battery Installation Procedures
on page 145.

Advertising