PPC-2000 User’s Guide

Chapter 5: LogicPro and Modbus Reference

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

213

Table 5.58

System Commands

Database

Offset

Modbus

Address

Name

Reset

After

Host

Write

Action

1

04051

Reload
Defaults

Reset

Load defaults to most run-time
parameters. The exceptions are
protocol, baud, parity, address,
system HW config, system com-
mands, system status, program
version, change data queue,
system error log, real time clock
and analog input calibration
data.

2

04052

Reserved

N/A

3

04053

Reserved

N/A

4

04054

RAM Clear
Reset

Reset

Clear RAM, reset controller and
load defaults

5

04055

Watchdog
Test

Reset

Force watchdog timeout

6

04056

Start Logic

Reset

Start logic program

7

04057

Reserved

N/A

8

04058

Stop Logic

Reset

Stop logic program

9

04059

Loop
Startup

Latched

0=Start control loops in off
mode. Undo not available.
1=Start control loops from last
mode stored in memory.

10

04060

AC
Frequency

Latched

0=60Hz
1=50Hz

11

04061

Logic Star-
tup

Latched

0=Start logic program when
commanded.
1=Start logic program on star-
tup.

12

04062

Reset PPC

Reset

Reset controller