Linear 0-1Vdc Input Example

For a sensor that measures light intensity between 0 and 500
Lumens and outputs a 0-1Vdc signal, set the following
parameters:

Table 3.7

Scaling Parameters for 0-1Vdc
Linear Input Example

Process Variable Retransmit

This feature allows you to output signals representing the
process variables of source channels or other analog inputs on
the heat and cool outputs of a retransmit channel. The analog
input selected as the PV Source of the retransmit channel is
output on the heat output. The analog input selected as the Set
Point Source
of the retransmit channel is output on the cool
output.

The output signals are scaled using the Min Set Point and Max
Set Point
and Heat/Cool Scale Hi and Heat/Cool Scale Lo
parameters. Figure 3.4 illustrates how the output signals are
related to the analog inputs by these scaling parameters.

Figure 3.4

Linear Scaling of the Analog Input
for Retransmit on the Heat or Cool
Output

Parameter

Setting

Units

Input Type

Linear -0.1 to 1 (v)

Units

Lumens

Input Signal Lo

0.0

mV

Input Signal Hi

1000.0

mV

PV Lo

0

Lumens

PV Hi

500.0

Lumens

Decimal Places

1

Heat/Cool Scale Lo

Heat/Cool Scale Hi

Min Set Point

Analog Input Range (Engineering Units)

Low

Max Set Point

Sensor Range

High

Sensor Range

Heat/Cool Output (% of Full Scale)