Chapter 2: Hardware Installation

PPC-2000 User’s Guide

40

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

1.

The name is shown for the first PPC-2000 in the system. See Digital I/O on page

132 for a complete explanation of digital I/O names.

2.

Both count and frequency are measured for the pulse input. See Inputs on page

127 for an explanation of analog input names.

Connecting Digital Inputs

The PPC-2010 module can accept digital inputs. When the
resistance of an input device is 27 kOhm or greater, the input
is considered off by the PPC-2000. When the resistance is 1
kOhm or less, the input is considered on.

To install a switch as a digital input, connect one lead to the DC
Common input return on the TB50. Connect the other lead to
the desired digital input on the TB50. Refer to Table 2.10 on
page 39
for screw terminal numbering.

Use the Digital I/O parameters to configure digital inputs.
Refer to Digital I/O on page 132.

Digital Out 35

35

PPC1: Proc 0.0.35

Digital Out 36

36

PPC1: Proc 0.0.36

Digital Out 37

37

PPC1: Proc 0.0.37

Digital Out 38

38

PPC1: Proc 0.0.38

Digital Out 39

39

PPC1: Proc 0.0.39

Digital Out 40

40

PPC1: Proc 0.0.40

Digital Out 41
SDAC Out 41

41

PPC1: Proc 0.0.41

Digital Out 42
SDAC Out 42

42

PPC1: Proc 0.0.42

Digital Out 43
SDAC Out 43

43

PPC1: Proc 0.0.43

Digital Out 44
SDAC Out 44

44

PPC1: Proc 0.0.44

Digital Out 45
SDAC Out 45

45

PPC1: Proc 0.0.45

Digital Out 46
SDAC Clock

46

PPC1: Proc 0.0.46

Global Alarm

47

PPC1: Proc 0.0.47

CPU Watchdog

48

PPC1: Proc 0.0.48

Com (DC Common for
Input Return)

49,50

N/A

Module I/O Number

TB-50

Terminal

AnaWin3 Name

(Dig I/O Spreadsheet)