Setting up ratio control, Setting up ratio control 110, Ratio channel’s set point. 110 – Watlow PPC-2000 User Manual

Page 134

Advertising
background image

Chapter 3: Operating with AnaWin 3

PPC-2000 User’s Guide

110

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

Figure 3.10 Relationship between the Master

Channel’s Process Variable and the
Ratio Channel’s Set Point.

Setting up Ratio Control

To set up ratio control:

1.

Set up the master channel as you would for a standard
closed-loop application. See Setting up Control Channels
on page 92
.

2.

Set up the ratio channel as you would for a standard
closed-loop application.

3.

Make the following additional settings on the ratio
channel:

a.

For

Set Point Source select the analog input that should

be used to determine the set point (the PV Source of the
master channel).

b.

Set the Set Point Ratio and Set Point Offset to create the
desired relationship between the analog input’s value
and the ratio channel’s set point.

c.

Set the Min Set Point to the lowest set point value the
ratio channel should ever have.

d.

Set the Max Set Point to the highest set point value the
ratio channel should ever have.

Set Point of the Ratio Channel

(Engineering Units)

Max Set Point

SP Offset

Sensor

Master Channel’s Process Variable

Sensor

Min Set Point

High

Range

Range

Low

SP Offset + Master PV * SP Ratio

(Engineering Units)