Adaptive Addendum

PPC-2000 User's Guide

0600-0049-0001 rev C

Watlow Anafaze

4

a. In the

PV

Source

field, choose the input that you want to

monitor or use as feedback for closed-loop control.

b. In the

Heat

Output

Dest

and/or

Cool

Output

Dest

fields,

choose the outputs that you want to use for closed-loop control.

c. Choose a

Heat/Cool Output Type

for each output.

d. Set the

Heat/Cool Cycle Time

for any outputs with

Heat/ Cool

Output Type

set to

Time Prop

.

4. On the

Digital I/O

spreadsheet:

a. Set the

Direction

for each I/O point to be used for control to

Output

.

5. On the

Channels

spreadsheet:

a. For channels other than the adaptive ones, if both heat and cool

outputs are used, set the

Spread

.

b. For each channel that will perform adaptive control, for the

Control Type

, choose

Adaptive

.

c. Set the

Set Point

to the desired value at least 40 engineering

units (typically degrees) above the process variable.

d. Set the

Control Mode

to

Auto

to begin adaptive closed-loop

control.

NOTE: Only channels 1 to 8 can be selected for adaptive control.