Ppc-2040 digital i/o, Ppc-2040 digital i/o 151 – Watlow PPC-2000 User Manual

Page 177

Advertising
background image

PPC-2000 User’s Guide

Chapter 4: Troubleshooting

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

151

PPC-2040 Digital I/O

Refer to the following descriptions of LED indicators when
troubleshooting the digital I/O module.

Green Status LED remains off, on, or blinks
incorrectly:
When the module is correctly functioning the
green LED blinks. If the LED remains off, on, or blinks
incorrectly, the module may not be functioning correctly.

Corrective Actions:

Make sure the rotary switch is set to the proper module ad-
dress. Each module must have a unique address.

Cycle power to PPC-2000 system.

Check that the modules are connected properly; refer to
Module Assembly on page 24.

Perform a RAM clear; refer to Resetting Closed-Loop
Control Parameters on page 156
.

Replace the module.

Green Status LED is blinking but inputs and/or
outputs are not reading correctly:

Corrective Actions:

Check to make sure the I/O wiring is correct. See Con-
necting I/O to the PPC-2040 on page 61.

Red Error LED remains on: Indicates at least one
digital output is in an incorrect state. The cause could be
an overloaded output or a failed output driver.

Corrective Actions:

Check the output circuits for shorts and repair if nec-
essary.

Check the load on the outputs to make sure that none of
them exceeds 150mA.

Check to make sure the I/O wiring is correct. See Con-
necting I/O to the PPC-2040 on page 61
.