PPC-2000 User’s Guide

Chapter 7: Specifications

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

235

Table 7.12

Digital Output Specifications

** The PPC-2010 has 48 built-in digital I/O points. 24 points
are outputs only. 22 of the outputs are user configurable for PID
control, alarms or logic outputs. The other 2 outputs are
dedicated to system status and global alarm. The remaining 24
I/O points are individual configurable as either inputs or
outputs.

Table 7.13

Serial Interface

Number

48**

Configuration

1 global alarm
1 system status (CPU watchdog timer)
22 control outputs
24 configurable as inputs or control outputs

Max. Voltage

24Vdc

Max. Current

100mA sink to power common continuous

Off State Leakage Cur-
rent, Outputs 1 to 24

100µA

Off State Leakage Cur-
rent, Outputs 25-48

5µA

On State Maximum
Voltage

0.7Vdc (output to common)

Number of Ports

2

Type

RS-232 3-wire or RS-485 5-wire

Modular Jacks

RS-232: 4 position, 4 conductor (phone handset)
RS-485: RJ12 6 position, 6 conductor

Isolation

40Vdc working, ± 200Vdc peak

Baud Rate

19200 default, configurable 9600 or 19200

Error Check

CRC

# of Controllers

1 with RS-232; 32 with RS-485

Protocol

Modbus RTU