Aitb connections, Aitb connections 47, Figure 2.30—an input key 47 – Watlow PPC-2000 User Manual
Page 71
Advertising
PPC-2000 User’s Guide
Chapter 2: Hardware Installation
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
47
Figure 2.30 An Input Key
AITB Connections
The AITB accommodates wiring thermocouples, RTDs, and
voltage/current linear inputs for all analog input modules.
Table 2.12 describes each analog module and Table 2.13 on
page 48 correlates the AITB labels with the sensor wire
connections for the various modules.
When connecting sensor wires, tighten to 0.5 – 0.6 Nm, or 4.5 –
5.4 inch-pound.
Table 2.12
Numbers and Types of Inputs by
Module Type
Module
Number
of
Inputs
Differential or
Single-ended
Note
PPC-2021
16
Differential
PPC-2022
32
Single-ended
PPC-2024
8
Differential
High Isolation
PPC-2025
16
Differential
High Isolation
P1
Indicates
component
side
Color indicates
key type
Advertising