Chapter 2: Hardware Installation

PPC-2000 User’s Guide

22

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

PPC-205x Jumper Settings

Each of the analog outputs on the PPC-205x modules may be
configured either as a voltage output or a current output. A
mixture of current and voltage outputs may be used on a
particular module. The jumpers only determine if the output
signal is current or voltage. The actual span of the signal is
software selectable. See Heat/Cool Output Type in Channels
section on page 119 for the various analog output signal
settings.

To configure an output, see Table 2.8 on page 22 and Figure 2.7
on page 23
to determine which jumper to set. Set the jumper in
the indicated position and orientation.

Table 2.8

PPC-205x Analog Out Jumpers

* Listed values are maximum ranges. Other ranges within these
limits may be selected in software.

Analog

Output

Jumper

PPC-2050

Jumper

PPC-2051

i (current)

Position*

v (voltage)

Position*

1

JU1

JU1

0-20mA

0-10Vdc

2

JU2

JU3

0-20mA

0-10Vdc

3

JU3

JU5

0-20mA

0-10Vdc

4

JU4

JU7

0-20mA

0-10Vdc

5

JU5

n/a

0-20mA

0-10Vdc

6

JU6

n/a

0-20mA

0-10Vdc

7

JU7

n/a

0-20mA

0-10Vdc

8

JU8

n/a

0-20mA

0-10Vdc