Using adaptive control – Watlow PPC-2000 User Manual

Page 5

Advertising
background image

Adaptive Addendum

PPC-2000 User's Guide

0600-0049-0001 rev C

Watlow Anafaze

3

This parameter has no effect on control if the Control Type for the loop is
set to an option other than Adaptive.
Values: Automatic (0) and 1 (1) to 600 seconds (600)
Default: Automatic (0)
Modbus Address (Channels 1 to 32): 49051 to 49082
Parameter Number: 28
LogicPro Driver: Database
LogicPro Address (Channels 1 to 32): 28.1 to 28.32

Tuning Gain

This parameter indicates the amount of delay in seconds in the load. This
characteristic of the load or plant has a significant impact on adaptive
control. A larger number indicates a longer delay between, for example
an increase in heater power and an increase in the temperature.
Values: Aggressive (0), Nominal (1), Damped 1 (2), Damped 2 (3),
Damped 3 (4) and Damped 4 (5)
Default: Nominal (1)
Modbus Address (Channels 1 to 32): 46551 to 46682
Parameter Number: 29
LogicPro Driver: Database
LogicPro Address (Channels 1 to 32): 29.1 to 29.32

Figure 1. The Effect of Tuning Gain on Recovery from a
Load Change

Using Adaptive Control

To set up adaptive control on one or more channels:

1. Open the

Spreadsheet Overview

screen in ANAWIN3.

2. On the

Inputs

spreadsheet for each analog input you have wired:

a. Choose the appropriate

Input

Type

for the sensor.

b. Choose

Units

.

c. For any linear voltage, current, or pulse sensors, set the linear

scaling parameters (

Input

Signal

Lo

,

Input

Signal

Hi

,

PV

Lo

,

and

PV

Hi

). See Setting up User Selectable Linear Inputs on

page 98 of the PPC-2000 User's Guide.

3. On the

Channels

spreadsheet for each channel: