Chapter 2: Hardware Installation

PPC-2000 User’s Guide

38

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

Figure 2.20 PPC-2010 Connection to TB50

NOTE!

If more than one module in the PPC system is
connected to a terminal board using a 50-pin SCSI
connector, label each end of each cable and each
terminal board with the address of the module to
which it should be connected.

TB50 Connections

Connect digital inputs and digital outputs for control signals,
alarms, and digital field I/O to the TB50. When connected to
the PPC-2010 Processor module, one pulse signal input and up
to five SDAC analog output modules can be connected to the
TB50. Table 2.10 on page 39 shows the TB50 pinout for use
with the PPC-2010.

Use 14 to 22 AWG wire. When making connections, tighten to
0.5 to 0.6 Nm, or 4.5 to 5.4 inch-pound.