Chapter 2

Feedback and I/O

This configuration is used when non-default settings are desired for minimum
and maximum speeds, but full range (0…10V) scaling from 0…60 Hz is still
desired.

In this example, a deadband from 0…2.5V and from 7.5…10V is created.
Alternatively, the analog input deadband could be eliminated while maintaining
the 15 and 45 Hz limits with the following changes:

P548 [Spd Ref A AnlgLo] = 15 Hz

P547 [Spd Ref A AnlgHi] = 45 Hz

Example 3

P255 [Anlg In Type], Bit 0 = “0” (Voltage)

P545 [Spd Ref A Sel] = “Analog In 1”

P547 [Spd Ref A AnlgHi] = 30 Hz

P548 [Spd Ref A AnlgLo] = 0 Hz

P61 [Anlg In1 Hi] = 10V

P62 [Anlg In1 Lo] = 0V

This is an application that requires only 30 Hz as a maximum output frequency
but is still configured for full 10V input. The result is that the resolution of the
input has been doubled, providing 1024 steps between 0 and 30 Hz.

15 Hz

45 Hz

60 Hz

0 Hz

P61 [Anlg In1 Hi]

10V

P522 [Min Fwd Speed]

P520 [Max Fwd Speed]

Motor Operating Range

Command Frequency

P62 [Anlg In1 Lo]

0V

P548 [Spd Ref A AnlgLo]

Slope defined by (Analog Volts)/(Command Frequency)

P547 [Spd Ref A AnlgHi]

Frequency Deadband

7.5…10 Volts

Frequency Deadband

0…2.5 Volts

10

9

8

7

6

5

4

3

2

1

0

0 10 20 30 40 50 60

Output Hertz

Inp

ut V

ol

ts