Motor Control

Chapter 4

A digital torque value to be used as a possible source for P675 and P680
respectively.

P677 [Trq Ref A AnlgHi]

and P682 [Trq Ref B AnlgHi] - Torque Reference A,

B Analog High
Used only when an analog input is selected as a torque reference according to
P676 or P681. Sets the torque value that corresponds to [Anlg In

n Hi] on an I/O

module or on the main control (product dependent). This establishes scaling
throughout the range.

P678 [Trq Ref A AnlgLo]

and P683 [Trq Ref B AnlgLo] - Torque Reference A,

B Analog Low
Used only when an analog input is selected as a torque reference according to
P676 [Trq Ref A Stpt] or P681 [Trq Ref B Stpt]. Sets the torque value that
corresponds to [Anlg In

n Lo] on an I/O module or on the main control (product

dependent). This establishes scaling throughout the range.

P679 [Trq Ref A Mult]

and P684 [Trq Ref B Mult] - Torque Reference A, B

Multiplier
A multiplier that is applied to the values referenced by P675 [Trq Ref A Sel] and
P680 [Trq Ref B Sel] respectively. A value of 1 leaves the reference unaffected.
Negative values invert the reference.

Refer to

Speed Torque Position on page 266

for an explanation of Speed Torque

Position mode choices for operating in various specific modes utilizing Internal
and/or External torque reference sources.