Option 1 “Adjust Freq”

If [Bus Reg Mode

n] is set to 1 “Adjust Freq” The Bus Voltage Regulator is

enabled. The Bus Voltage Regulator setpoint follows “Bus Reg Curve 1” below a
DC Bus Memory of 650V DC and follows the “DB Turn On” above a DC Bus
Memory of 650V DC (

Table 5

). For example, with a DC Bus Memory at 684V

DC, the adjust frequency setpoint is 750V DC.

Below you can see the DC bus is being regulated as the speed is sacrificed to be
sure the drive does not trip on over voltage.

Figure 3 -

PowerFlex 750-Series Bus Regulation – Adjust Frequency

Option 2 “Dynamic Brak”

If [Bus Reg Mode

n] is set to 2 “Dynamic Brak” The Dynamic Brake Regulator is

enabled. In Dynamic Brake mode the Bus Voltage Regulator is turned off. The
“DB Turn On” and turn off curves apply. For example, with a DC Bus Memory at
684V DC, the Dynamic Brake Regulator turns on at 750V DC and turns back
off at 742V DC. The Dynamic Brake mode can operate differently depending
upon the setting of P382 [DB Resistor Type] either External or Internal.

900

800

700

600

500

400

300

200

100

0

12

10

8

6

4

2

0

-1 0 1 2 3 4 5 6 7 8 9

DC Bus Voltage

Speed Feedback

DC bus is regulated under the over voltage trip point.

Motor stops in just under 7 seconds instead

of the programmed 1 second decel.

Seconds

DC B

us

V

olt

s

10

V

olt
s =
B

ase
Sp

ee

d